Gas detection systems raise the alarm when toxic gases build up, oxygen runs low or an explosive mixture forms. To do that when it matters, they have to be checked, calibrated and, where needed, adjusted at regular intervals. How and how often is set out in two information sheets from the German social accident insurance institution for the raw materials and chemical industry (BG RCI), both in the edition of October 2023:
- T 021 (DGUV Information 213-056) for toxic gases and vapours and for oxygen
- T 023 (DGUV Information 213-057) for explosion protection
The digital inspection process with which a refinery checks around 500 gas detectors is based on these sheets as well. This article sums up what they require for fixed gas detection systems. It replaces neither the sheets nor your risk assessment; you will find the sources in full at the end.
Calibrating means comparing, adjusting means setting
In everyday use the two words are often used interchangeably; the sheets keep them strictly apart. Calibrating compares the reading with a test gas of known concentration without changing anything. Adjusting means resetting the zero point and the sensitivity with zero gas and test gas.
The order is fixed: zero point first, then sensitivity, and it is advisable to check the zero point once more at the end. As a rule the test gas must match the target gas, the gas the system is meant to monitor. If the target gas is hard to handle, a substitute test gas is allowed; it is agreed with the device manufacturer and documented.
Four checks, three qualifications
Maintenance is tiered. Each level includes the ones below and replaces them when both are due at the same time.
- Visual inspection, by an instructed person: external damage, dirty gas inlets, the sampling system and whether the system is ready to measure, without alarm or special state.
- Function test, by qualified specialist staff: the visual inspection, plus applying zero gas and test gas, assessing the reading (calibration), adjusting if necessary and assessing the response time against the manufacturer’s data. Switching functions need not be triggered.
- System test, by a competent person: the function test, plus every safety function through to its trigger, such as a ventilation fan starting or the alarm going out, a target/actual comparison of the safety-relevant settings (measuring range, target gas, alarm thresholds, switching outputs) and the signalling and recording equipment.
- Review of records, also by a competent person: are all checks documented, the resulting measures carried out promptly, installation documents and operating instructions up to date?
How often to check
For fixed gas detection systems both sheets recommend the same maximum intervals:
- Visual inspection: 1 month
- Function test: 4 months, with self-monitoring functions at most 1 year
- System test: 1 year
- Review of records: 3 years
These intervals only apply once there is experience with the device under exactly these conditions. Without it, commissioning is followed by two function tests four weeks apart, then further ones every two months. Only when no readjustment is needed may you move to the maximum intervals. If adjustment is needed within the first eight weeks, checks become more frequent.
If the risk assessment under section 3 (6) of the German Ordinance on Industrial Safety and Health (BetrSichV) results in shorter or longer intervals, those apply. And after the measuring range has been exceeded, a sensor may have changed permanently: an extra function test is then due soon, and another one about a week later.
When to adjust
Not every deviation calls for adjustment. The limits depend on the application:
- Toxic gases (T 021): as a rule when the zero reading deviates by more than ±10 % of the (main) alarm value or the sensitivity by more than ±20 % of the target value. The test gas concentration should be known to within ±10 % where possible and ensure sufficient accuracy around the alarm thresholds.
- Explosion protection (T 023): when the deviation is more than ±5 % LEL up to 50 % of the lower explosive limit (LEL), and more than ±10 % of the target value above that, for a measuring range up to 100 % LEL. The test gas is usually around 50 % LEL, at least above the main alarm, and known to within ±5 % where possible.
An example from the image above: test gas at 50 % LEL, the reading before adjustment 48.2 % LEL. The deviation of 1.8 % LEL is within the limit of T 023.
Response time and t90
Function and system tests also assess how quickly a device responds. The sheets define the response time for this: the time from a sudden change from clean air to test gas until the reading reaches a set share of its final value. For t90 that share is 90 %. It is assessed against the data in the manufacturer’s operating manual.
What belongs in the record
Every check is documented, and electronic records are expressly allowed. For function and system tests the record includes at least:
- which system (plant section, measuring point)
- the composition of the test gases used
- the readings with zero gas and test gas before and after calibration and adjustment
- the assessment of the response times
- defects found and work carried out
- date and unique identification of the person
For the system test, deviations of the settings from their target values are added. Records of visual inspections and function tests are kept until the next review of records, those of system tests and reviews of records for ten years.
From information sheet to digital inspection process
At that refinery these requirements sit in the process model of an inspection app on the flyze.platform: which check is due at which interval, which steps belong to it and what has to be recorded. The app guides the inspectors through visual, function and system tests, takes readings straight from the sensor via OPC, enters the T90 time by itself and turns every inspection into a record with values, inspector and time. What this looks like day to day is shown in the case study, linked at the top and under “Read more”.
One thing holds throughout: the gas detection system and its safety functions stay as they are; the app plans, guides and documents the checks.
The sources in full
T 021, DGUV Information 213-056
Gas detection systems and devices for toxic gases/vapours and oxygen: use and operation (in German)
Go to the source: T 021, DGUV Information 213-056T 023, DGUV Information 213-057
Gas detection systems and devices for explosion protection: use and operation (in German)
Go to the source: T 023, DGUV Information 213-057
